Por favor, use este identificador para citar o enlazar este ítem:https://uvadoc.uva.es/handle/10324/57240
Título
Power consumption analysis of electrical installations at healthcare facility
Autor
Año del Documento
2017
Editorial
MDPI
Descripción
Producción Científica
Documento Fuente
Energies, 2017, vol. 10, n. 1, p. 64
Abstract
This paper presents a methodology for power consumption estimation considering harmonic and interharmonic content and then it is compared to the power consumption estimation commonly done by commercial equipment based on the fundamental frequency, and how they can underestimate the power consumption considering power quality disturbances (PQD). For this purpose, data of electrical activity at the electrical distribution boards in a healthcare facility is acquired for a long time period with proprietary equipment. An analysis in the acquired current and voltage signals is done, in order to compare the power consumption centered in the fundamental frequency with the generalized definition of power consumption. The results obtained from the comparison in the power consumption estimation show differences between 4% and 10% of underestimated power consumption. Thus, it is demonstrated that the presence of harmonic and interharmonic content provokes a significant underestimation of power consumption using only the power consumption centered at the fundamental frequency.
Materias Unesco
33 Ciencias Tecnológicas
Palabras Clave
Energy consumption estimation
Power quality
Data acquisition
Data analysis
Revisión por pares
SI
Patrocinador
SEP-CONACYT, under grant 222453-2013
FOMIX, under grant QRO-2014-C03-250269
FOFIUAQ-FIN201613
FOMIX, under grant QRO-2014-C03-250269
FOFIUAQ-FIN201613
Version del Editor
Propietario de los Derechos
© 2017 The Author(s)
Idioma
eng
Tipo de versión
info:eu-repo/semantics/publishedVersion
Derechos
openAccess
Aparece en las colecciones
Files in questo item
La licencia del ítem se describe como Atribución 4.0 Internacional