<?xml version="1.0" encoding="UTF-8"?><?xml-stylesheet type="text/xsl" href="static/style.xsl"?><OAI-PMH xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/ http://www.openarchives.org/OAI/2.0/OAI-PMH.xsd"><responseDate>2026-04-30T00:21:36Z</responseDate><request verb="GetRecord" identifier="oai:uvadoc.uva.es:10324/81689" metadataPrefix="edm">https://uvadoc.uva.es/oai/request</request><GetRecord><record><header><identifier>oai:uvadoc.uva.es:10324/81689</identifier><datestamp>2026-01-16T20:03:31Z</datestamp><setSpec>com_10324_38</setSpec><setSpec>col_10324_852</setSpec></header><metadata><rdf:RDF xmlns:rdf="http://www.w3.org/1999/02/22-rdf-syntax-ns#" xmlns:doc="http://www.lyncode.com/xoai" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:ore="http://www.openarchives.org/ore/terms/" xmlns:dcterms="http://purl.org/dc/terms/" xmlns:ds="http://dspace.org/ds/elements/1.1/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:edm="http://www.europeana.eu/schemas/edm/" xsi:schemaLocation="http://www.w3.org/1999/02/22-rdf-syntax-ns# http://www.europeana.eu/schemas/edm/EDM.xsd">
<edm:ProvidedCHO rdf:about="https://uvadoc.uva.es/handle/10324/81689">
<dc:contributor>Tejero González, Ana</dc:contributor>
<dc:contributor>González González, Sergio Lorenzo</dc:contributor>
<dc:contributor>Universidad de Valladolid. Escuela de Ingenierías Industriales</dc:contributor>
<dc:creator>Calleja Pastor, Hugo</dc:creator>
<dc:date>2025</dc:date>
<dc:description>Los objetivos orientados a la descarbonización de los edificios implican la &#xd;
necesidad de instalaciones de energía renovable in situ o cercanas. Entre las &#xd;
aplicaciones de energía renovable menos estudiadas se encuentra el uso de &#xd;
energía geotérmica somera a través de intercambiadores de calor tierra aire (Earth&#xd;
to-Air Heat Exchangers, EAHE). Este Trabajo Fin de Grado tiene como principal &#xd;
objetivo caracterizar el rendimiento térmico de un sistema EAHE instalado en el &#xd;
edifico IndUVa, edificio de consumo de energía casi nulo (near Zero Energy Building &#xd;
nZEB) en la Universidad de Valladolid y revisar la monitorización de otro sistema &#xd;
EAHE instalado en el edifico LUCIA, edificio de consumo de energía casi nulo en la &#xd;
misma institución. El estudio se centra en la temporada de calefacción (octubre a &#xd;
marzo). Para ello, se miden tanto las temperaturas del terreno a distinta &#xd;
profundidad, como las condiciones del aire a la entrada y salida de los sistemas de &#xd;
ambos edificios. Para caracterizar el rendimiento térmico del sistema EAHE &#xd;
instalado en el edifico IndUVa, también se miden los caudales de aire para verificar &#xd;
los valores proporcionados por el sistema de supervisión y adquisición de datos &#xd;
(SCADA) del edificio. Los resultados permiten una evaluación de la capacidad de &#xd;
calefacción del sistema EAHE. Si bien las temperaturas de suministro siguen la &#xd;
tendencia decreciente de las temperaturas del suelo a lo largo del invierno, los &#xd;
saltos de temperatura logrados aumentan a medida que se endurecen las &#xd;
temperaturas exteriores. Finalmente, se comprueba que el sistema EAHE del &#xd;
edificio IndUVa cubre entre el 25% y el 34% de las cargas térmicas relacionadas con &#xd;
la ventilación durante toda la temporada de calefacción.</dc:description>
<dc:description>The objectives aimed at building decarbonization involve the need for on-site or &#xd;
nearby renewable energy installations. Among the less studied renewable energy &#xd;
applications is the use of shallow geothermal energy through Earth-to-Air Heat &#xd;
Exchangers (EAHE). This Bachelor's Thesis primarily aims to characterize the &#xd;
thermal performance of an EAHE system installed in the IndUVa building, a near &#xd;
Zero Energy Building (nZEB) at the University of Valladolid, and to review the &#xd;
monitoring of another EAHE system installed in the LUCIA building, also a near Zero &#xd;
Energy Building at the same institution. &#xd;
The study focuses on the heating season (October to March). For this purpose, &#xd;
ground temperatures at various depths are measured, as well as the air conditions &#xd;
at the inlet and outlet of the systems in both buildings. To characterize the thermal &#xd;
performance of the EAHE system in the IndUVa building, air flow rates are also &#xd;
measured to verify the values provided by the building's Supervision, Control, and &#xd;
Data Acquisition (SCADA) system. The results allow for an evaluation of the heating &#xd;
capacity of the EAHE system. While the supply temperatures follow the decreasing &#xd;
trend of ground temperatures throughout the winter, the achieved temperature &#xd;
gains increase as outdoor temperatures become more severe. Finally, it is &#xd;
confirmed that the EAHE system in the IndUVa building covers between 25% and &#xd;
34% of the ventilation-related thermal loads during the entire heating season.</dc:description>
<dc:format>application/pdf</dc:format>
<dc:identifier>https://uvadoc.uva.es/handle/10324/81689</dc:identifier>
<dc:language>spa</dc:language>
<dc:subject>3322.05 Fuentes no Convencionales de Energía</dc:subject>
<dc:title>Estudio del comportamiento térmico  estacional de los intercambiadores tierra-aire  de los edificios IndUVa y LUCIA</dc:title>
<dc:type>info:eu-repo/semantics/bachelorThesis</dc:type>
<edm:type>TEXT</edm:type>
</edm:ProvidedCHO>
<ore:Aggregation rdf:about="https://uvadoc.uva.es/handle/10324/81689#aggregation">
<edm:aggregatedCHO rdf:resource="https://uvadoc.uva.es/handle/10324/81689"/>
<edm:dataProvider>UVaDOC. Repositorio Documental de la Universidad de Valladolid</edm:dataProvider>
<edm:isShownAt rdf:resource="https://uvadoc.uva.es/handle/10324/81689"/>
<edm:isShownBy rdf:resource="https://uvadoc.uva.es/bitstream/10324/81689/1/TFG-I-3342.pdf"/>
<edm:provider>Hispana</edm:provider>
<edm:rights rdf:resource="http://creativecommons.org/licenses/by-nc-nd/4.0/"/>
</ore:Aggregation>
<edm:WebResource rdf:about="https://uvadoc.uva.es/bitstream/10324/81689/1/TFG-I-3342.pdf">
<edm:rights rdf:resource="http://creativecommons.org/licenses/by-nc-nd/4.0/"/>
</edm:WebResource>
</rdf:RDF></metadata></record></GetRecord></OAI-PMH>