Por favor, use este identificador para citar o enlazar este ítem:https://uvadoc.uva.es/handle/10324/65858
Título
Nitrogen removal in domestic wastewater. Effect of nitrate recycling and COD/N ratio
Año del Documento
2018
Documento Fuente
Chemosphere, 212, pp. 8-14
Abstract
A denitrification/nitrification pilot plant was designed, built and put into operation, treating the effluent of an anaerobic reactor. The operation of the plant examined the effect of the nitrate recycling and the COD/N ratio on the nitrogen and the remaining organic matter removal at 18 °C. The system consisted of a two-stage treatment process: anoxic and aerobic. The hydraulic retention time (HRT) of the system was 1 h for the anoxic bioreactor and 2 h for the aerobic one. The increase in the nitrate recycling ratio did not cause a significant improvement in the nitrogen removal due to the insufficient carbon source. The wastewater to be treated had a C/N ratio of 1.1 showing a lack of organic carbon. The addition of methanol was a key point in the denitrification process used as a model for the traditional wastewater by-pass in the WWTP. The maximum nitrogen and organic matter removal (87.1% and 96%, respectively) was achieved with a nitrate recycling ratio of 600% and a C/N of 8.25, adjusted by methanol addition.
ISSN
0045-6535
Revisión por pares
SI
Patrocinador
European Regional Development Fund, the IPT-2011-1078-310000 project,and the INNPACTO 2011 program of the Ministry of Economy and Competitiveness
Idioma
eng
Tipo de versión
info:eu-repo/semantics/publishedVersion
Derechos
openAccess